<?xml version="1.0" encoding="utf-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Journal Publishing DTD v1.2 20190208//EN" "https://jats.nlm.nih.gov/publishing/1.2/JATS-journalpublishing1.dtd">
<article xmlns:xlink="http://www.w3.org/1999/xlink">
  <front>
    <article-meta>
      <title-group>
        <article-title>A Simulator Independent Dynamic Effectiveness-NTU Model for Heat-Exchanger Performance Prediction under Flow, Temperature, and Fouling Dependent Operation</article-title>
      </title-group>
      <contrib-group content-type="author">
        <contrib contrib-type="person">
          <name>
            <surname>Ali</surname>
            <given-names>Hassanin M.</given-names>
          </name>
          <email>eng.hassanin.mehsin@uobabylon.edu.iq</email>
          <xref ref-type="aff" rid="aff-1"/>
        </contrib>
      </contrib-group>
      <aff id="aff-1">
        <institution>Department of Chemical Engineering, College of Engineering, University of Babylon, Babil 51001</institution>
        <country>Iraq</country>
      </aff>
      <history>
        <date date-type="received" iso-8601-date="2026-10-11">
          <day>11</day>
          <month>10</month>
          <year>2026</year>
        </date>
      </history>
    <pub-date pub-type="epub"><day>11</day><month>10</month><year>2026</year></pub-date></article-meta>
  </front>
  
  
<body id="body">
    <p id="_paragraph-8">
      <bold id="_bold-10">Nomenclature</bold>
    </p>
    <fig id="fig1">
      <label>Figure 1</label>
      <caption>
        <p id="_paragraph-9"/>
      </caption>
      <graphic id="_graphic-1" mimetype="image" mime-subtype="png" xlink:href="image1.png"/>
    </fig>
    <p id="_paragraph-10"><bold id="_bold-11">Subscripts: </bold>c, cold stream / clean; h, hot stream; i, inlet; o, outlet; f, fouled / film; w, wall; min, max, minimum and maximum heat-capacity rate; d, deposition; r, removal.</p>
    <sec id="_heading-1">
      <title>Introduction</title>
      <p id="_paragraph-11">Heat exchangers recover a large fraction of the energy reused in crude-oil refining, petrochemicals, power generation and food processing, so their thermal performance bears directly on plant energy efficiency, operating cost and greenhouse-gas emissions. That performance is not fixed. Deposits accumulate on the transfer surface, add a thermal resistance that grows with time, and progressively starve the exchanger of duty. In refinery pre-heat trains this fouling penalty is paid as additional furnace firing, lost throughput and unscheduled shutdowns <xref id="_xref-1" ref-type="bibr" rid="bib1">[1]</xref>, <xref id="_xref-2" ref-type="bibr" rid="bib2">[2]</xref>.</p>
      <p id="_paragraph-12">In spite of the economic importance of this issue, conventional design still considers fouling on a single immutable parameter: an average value derived from tabulated data and applied just once to the clean overall coefficient in the design phase <xref id="_xref-3" ref-type="bibr" rid="bib3">[3]</xref>. There are two problems with this lumped, steady-state device. It assumes fouling is a fixed allowance, not an evolving process so the exchanger is either clean or fully fouled with no in-between consequences. More seriously, it ignores the parameters that really control deposition local surface temperature and wall shear stress, and so flow rate <xref id="_xref-4" ref-type="bibr" rid="bib4">[4]</xref>, <xref id="_xref-5" ref-type="bibr" rid="bib5">[5]</xref>. Identical geometry of two exchangers which work with different velocities or film temperatures foul as fouling at different rates and settling at different asymptotic states, yet the fixed factor gives them the same number.</p>
      <p id="_paragraph-13">The specific thermal relations that were necessary to do better have long been established. The methods based on the steady-flow energy balance, both log-mean-temperature-difference (LMTD) and effectiveness–number-of-transfer-units (ε–NTU), provide exact and complete descriptions of the thermal performance of an exchanger with a given overall coefficient <xref id="_xref-6" ref-type="bibr" rid="bib6">[6]</xref>, <xref id="_xref-7" ref-type="bibr" rid="bib7">[7]</xref>,<xref id="_xref-8" ref-type="bibr" rid="bib8">[8]</xref>. The only difference at this stage is which variables are considered known, the ε–NTU form is the obvious choice for an installed unit, whose area must be fixed and whose outlet temperatures (and thus duty) fall as the coefficient deteriorates, just what fouling is. But both approaches, however, assume a constant coefficient and do not discuss its evolution with time. Time-varying versions of the ε–NTU concept have been developed for step changes in inlet conditions <xref id="_xref-9" ref-type="bibr" rid="bib9">[9]</xref>, and for units undergoing discharge of matter <xref id="_xref-10" ref-type="bibr" rid="bib10">[10]</xref>, both confirming that the framework extends into the time domain, but neither addresses fouling, which occurs at a much slower time scale than the thermal transients (order of minutes) we consider here (weeks to months), so the results from our transient treatment can be assumed instantaneous and well-approximated by quasi-steady heat exchanger analysis.</p>
      <p id="_paragraph-14">Epstein organized fouling by the style of the mechanism and associated sequences of deposition and removal events, two attributes that reappear in every quantitative model: net growth is equal to a deposition term minus a removal term, with both dependent on local surface temperature and shear. The earliest and still most influential statement of this balance has been given by Kern and Seaton writing the net rate as a constant deposition flux minus a removal term proportional to the amount accumulated <xref id="_xref-11" ref-type="bibr" rid="bib11">[11]</xref>, integration yielding the characteristic asymptotic approach to a plateau which is still for many observers the default description under steady conditions <xref id="_xref-12" ref-type="bibr" rid="bib12">[12]</xref>. Ebert and Panchal incorporated a complementary threshold for the chemical-reaction fouling of crude oil <xref id="_xref-13" ref-type="bibr" rid="bib13">[13]</xref>, and subsequent refinements confirm that dep increases with surface temperature via an Arrhenius factor while removal compliance increases with wall shear, and velocity <xref id="_xref-14" ref-type="bibr" rid="bib14">[14]</xref>.</p>
      <p id="_paragraph-15">The current state of the art consists of distributed first-principles models building on the these laws. Coletti and Macchietto investigated Local fouling rates, a moving deposit boundary and the deposit–flow interaction in a multi-pass shell-and-tube unit <xref id="_xref-15" ref-type="bibr" rid="bib15">[15]</xref>; Diaz-Bejarano to an aged and removable multi-component fouling, supporting full cycles of fouling–cleaning which have been used in plant diagnostics and pre-heat-train optimizations since <xref id="_xref-16" ref-type="bibr" rid="bib16">[16]</xref>. These models are quite strict; they, however, require determining coupled partial differential equations outside specialized software and their computational weight is frequently a lot of in excess of the keyword regarding the data from the plant plane to drive them. A comparative data-driven approach predicts fouling resistance or deposit thickness through neural, support-vector and related models, while model-based methods deduce fouling from excess thermal and hydraulic loads or include it into predictive control <xref id="_xref-17" ref-type="bibr" rid="bib17">[17]</xref>, <xref id="_xref-18" ref-type="bibr" rid="bib18">[18]</xref>, <xref id="_xref-19" ref-type="bibr" rid="bib19">[19]</xref>, <xref id="_xref-20" ref-type="bibr" rid="bib20">[20]</xref>. Such models match their training range well, but are poor at extrapolating and neither provide closed-form sensitivities of duty versus velocity nor temperature.</p>
      <p id="_paragraph-16">Thermal methods thus precisely characterize performance at a particular coefficient, asymptotic and threshold laws indicate how the coefficient degrades, distributed models link those two rigorously but at high computational cost in dedicated software, and data-driven models are good fits but offer neither generalization nor sensitivity. Knowledgeable us do not recognize a compact treatment that concurrently gives explicit coupling of the ε–NTU heat field to an asymptotic fouling law with mechanistic velocity and temperature dependence, closed-form sensitivity coefficients for the major execution measures, one dimensionless degradation set, and sufficient computational cost in order for possible online applications without requiring any commercial simulator.</p>
      <p id="_paragraph-17">This paper occupies that niche. We derive, entirely from first principles and free of a commercial simulator, a quasi-steady dynamic model in which coupled with an asymptotic Kern–Seaton fouling law are the energy balance, LMTD relation and ε–NTU formulation. Everything is classical, in short; the novelty is in their synthesis being closed, and what that means it makes computable. First, fouling resistance progresses through a single ordinary differential equation where its deposition and removal terms are explicit power laws in tube velocity and an Arrhenius function of film temperature, so flow rate and temperature appear mechanistically, rather than as fitted parameters. Second, at each instant, the thermal field is solved quasi-steadily based on the exact ε–NTU relations; hence, the global coefficient, duty, effectiveness and both outlet temperatures change in a consistent way with respect to the deposit. Third, we derive closed form normalized sensitivity coefficients for the effectiveness, the duty and overall coefficient which rank how strongly each operating variable moves the performance. A fourth finding is that the asymptotic loss of effectiveness and duty collapse on a single dimensionless group, the fouling-degradation number Θ = Uc Rf*, which acts as a compact design criterion.</p>
      <p id="_paragraph-18">The rest of the paper is structured as follows: Section 2 presents the physical picture and assumptions while Section 3 derives all of the governing relation with their SI units. In Section 4, a numerical methodology and case study are presented; Section 5 verifies the implementation with various analytical limits. The results for dynamic degradation, the velocity and temperature dependences, the sensitivity ranking and the uncertainty analysis are presented in Section 6. Discussed against published approaches in Section 7, the conclusions are provided in Sections 8.</p>
      <sec id="heading-90f771a745f4c0da48a4df19786f0498">
        <title>2. Model Development</title>
        <p id="paragraph-ab6d61be96f09530a7292bac754e18d4">
          <bold id="bold-438d9e29ddc21e2390268f87de4db53c">2.1 Physical picture</bold>
        </p>
        <p id="_paragraph-19">We consider a single-phase, two-stream shell-and-tube heat exchanger operated in counterflow, in which a hot process stream is cooled by a colder stream. On the surface separating the two fluids a fouling layer accumulates, adding a thermal resistance in series with the two convective films and the tube wall. The layer grows because material is deposited from the fluid faster than the flow can scour it away; as it thickens, the deposition and removal rates approach one another and the resistance tends to a plateau. This is the asymptotic behavior first rationalized by Kern and Seaton.</p>
        <p id="_paragraph-20">Two-time scales are present and they are widely separated. The thermal residence time of the fluids and the time for the temperature field to respond to a disturbance are of the order of seconds to minutes, whereas the fouling layer develops over days to months. This separation is the physical justification for a quasi-steady treatment: on the slow fouling clock, the exchanger is, at every instant, in thermal steady state. We therefore solve the steady ε–NTU relations at each moment for the current value of the fouling resistance, and let that resistance evolve according to a first-order deposition–removal law. The coupling runs in both directions, because the fouling rate depends on the surface (film) temperature, which is itself set by the current thermal state of the exchanger.</p>
        <p id="paragraph-ddc418c2b15dc4d869fdbe5d881b0d99">
          <bold id="bold-0f28576d5b12d156e562d1d319c1b9a0">2.2 Assumptions and their justification</bold>
        </p>
        <p id="_paragraph-21">The model rests on the following assumptions. Each is stated with the physical reasoning that supports it and, where relevant, the range over which it holds.</p>
        <list list-type="bullet" id="list-c329396ee6d3048642a8d8422ec8909f">
          <list-item>
            <p><bold id="_bold-12">A1 — Quasi-steady thermal field. </bold>Because the fouling time constant (tens of days, Section 6) exceeds the thermal response time (minutes) by three to four orders of magnitude, the temperature field equilibrates essentially instantaneously relative to deposit growth. The exchanger is treated as being in thermal steady state at every instant while the fouling resistance advances in time.</p>
          </list-item>
          <list-item>
            <p><bold id="_bold-13">A2 — Constant</bold><bold id="_bold-14">, </bold><bold id="_bold-15">mean physical properties. </bold>Specific heats, densities, viscosities and conductivities are evaluated at the mean bulk temperature of each stream and held constant. For the moderate temperature spans of a single unit this introduces only a small error; strongly temperature-dependent properties would require the step-wise evaluation noted as a limitation in Section 7.</p>
          </list-item>
          <list-item>
            <p><bold id="_bold-16">A3 — Uniform overall coefficient at each instant. </bold>The overall coefficient is taken as uniform over the surface at any given time (it still varies in time as fouling proceeds). This is the standard premise of both the LMTD and ε–NTU methods and is accurate when the streams are well mixed in cross-section.</p>
          </list-item>
          <list-item>
            <p><bold id="_bold-17">A4 — Adiabatic shell and negligible axial effects. </bold>Heat loss to the surroundings and axial conduction in the wall and fluids are neglected, consistent with a well-insulated unit operating at a high Péclet number.</p>
          </list-item>
          <list-item>
            <p><bold id="_bold-18">A5 — Single-phase, sensible-heat duty. </bold>No boiling or condensation occurs; both streams exchange sensible heat only. Two-phase operation is outside the present scope.</p>
          </list-item>
          <list-item>
            <p><bold id="_bold-19">A6 — Thin deposit, lumped fouling resistance. </bold>The deposit is thin relative to the tube radius (for the case of Section 4 its thickness is of order 0.1 mm against a tube radius of tens of millimeters), so the change in flow area and heat-transfer area is negligible and the deposit can be represented by a single series thermal resistance referred to the reference area.</p>
          </list-item>
          <list-item>
            <p><bold id="_bold-20">A7 — Deposition–removal kinetics. </bold>Net deposit growth is the difference between a deposition term, taken as an Arrhenius function of film temperature and a power law in velocity (mass-transfer/surface-reaction control), and a removal term proportional to the deposit already present and to a power of velocity (shear scouring). This is the Kern–Seaton form with the temperature and velocity dependences made explicit in the manner of Ebert and Panchal and Yeap.</p>
          </list-item>
          <list-item>
            <p><bold id="_bold-21">A8 — Time-invariant kinetic parameters. </bold>The deposition and removal pre-factors and the activation energy are constant, i.e. the feed composition does not change over the horizon considered. Feed variability would make these parameters time-dependent (Section 9).</p>
          </list-item>
        </list>
        <sec id="heading-d4a482b1bd8f0371bfa948cff34767fb">
          <title>3. Mathematical Derivations</title>
          <p id="paragraph-460d8ad0e6ba7027ec34537db0da15e7">
            <bold id="bold-2fc86bc4217c5c55133c8cadfa5b625d"> 3.1 Steady-flow energy balance</bold>
          </p>
          <p id="_paragraph-22">Applying the first law to each stream under steady flow, with no shaft work and no heat loss (A4), the duty transferred equals the enthalpy change of each stream:</p>
          <p id="_paragraph-23"><italic id="_italic-3">Q = C</italic><sub id="_subscript-3"><italic id="_italic-4">h</italic></sub><italic id="_italic-5"> (T</italic><sub id="_subscript-4"><italic id="_italic-6">h,i</italic></sub><italic id="_italic-7"> − T</italic><sub id="_subscript-5"><italic id="_italic-8">h,o</italic></sub><italic id="_italic-9">)</italic>(1)</p>
          <p id="_paragraph-24"><italic id="_italic-10">Q = C</italic><sub id="_subscript-6"><italic id="_italic-11">c</italic></sub><italic id="_italic-12"> (T</italic><sub id="_subscript-7"><italic id="_italic-13">c,o</italic></sub><italic id="_italic-14"> − T</italic><sub id="_subscript-8"><italic id="_italic-15">c,i</italic></sub><italic id="_italic-16">)</italic>(2)</p>
          <p id="_paragraph-25">where the heat-capacity rates are</p>
          <p id="_paragraph-26"><italic id="_italic-17">C</italic><sub id="_subscript-9"><italic id="_italic-18">h</italic></sub><italic id="_italic-19"> = ṁ</italic><sub id="_subscript-10"><italic id="_italic-20">h</italic></sub><italic id="_italic-21"> c</italic><sub id="_subscript-11"><italic id="_italic-22">p,h</italic></sub><italic id="_italic-23"> ,     C</italic><sub id="_subscript-12"><italic id="_italic-24">c</italic></sub><italic id="_italic-25"> = ṁ</italic><sub id="_subscript-13"><italic id="_italic-26">c</italic></sub><italic id="_italic-27"> c</italic><sub id="_subscript-14"><italic id="_italic-28">p,c</italic></sub>(3)</p>
          <p id="_paragraph-27"><italic id="_italic-29">Q</italic> =  heat-transfer rate (duty), W</p>
          <p id="_paragraph-28"><italic id="_italic-30">C</italic><sub id="_subscript-15"><italic id="_italic-31">h</italic></sub><italic id="_italic-32">, C</italic><sub id="_subscript-16"><italic id="_italic-33">c</italic></sub> =  heat-capacity rates of hot and cold streams, W K⁻¹</p>
          <p id="_paragraph-29"><italic id="_italic-34">ṁ</italic><sub id="_subscript-17"><italic id="_italic-35">h</italic></sub><italic id="_italic-36">, ṁ</italic><sub id="_subscript-18"><italic id="_italic-37">c</italic></sub> =  mass flow rates, kg s⁻¹</p>
          <p id="_paragraph-30"><italic id="_italic-38">c</italic><sub id="_subscript-19"><italic id="_italic-39">p,h</italic></sub><italic id="_italic-40">, c</italic><sub id="_subscript-20"><italic id="_italic-41">p,c</italic></sub> =  specific heats, J kg⁻¹ K⁻¹</p>
          <p id="_paragraph-31"><italic id="_italic-42">T</italic><sub id="_subscript-21"><italic id="_italic-43">h,i</italic></sub><italic id="_italic-44">, T</italic><sub id="_subscript-22"><italic id="_italic-45">h,o</italic></sub> =  hot-stream inlet and outlet temperatures, K (or °C)</p>
          <p id="_paragraph-32"><italic id="_italic-46">T</italic><sub id="_subscript-23"><italic id="_italic-47">c,i</italic></sub><italic id="_italic-48">, T</italic><sub id="_subscript-24"><italic id="_italic-49">c,o</italic></sub> =  cold-stream inlet and outlet temperatures, K (or °C)</p>
          <p id="_paragraph-33">It is convenient to identify the smaller and larger of the two heat-capacity rates and their ratio:</p>
          <p id="_paragraph-34"><italic id="_italic-50">C</italic><sub id="_subscript-25"><italic id="_italic-51">min</italic></sub><italic id="_italic-52"> = min(C</italic><sub id="_subscript-26"><italic id="_italic-53">h</italic></sub><italic id="_italic-54">, C</italic><sub id="_subscript-27"><italic id="_italic-55">c</italic></sub><italic id="_italic-56">) ,   C</italic><sub id="_subscript-28"><italic id="_italic-57">max</italic></sub><italic id="_italic-58"> = max(C</italic><sub id="_subscript-29"><italic id="_italic-59">h</italic></sub><italic id="_italic-60">, C</italic><sub id="_subscript-30"><italic id="_italic-61">c</italic></sub><italic id="_italic-62">) ,   C</italic><sub id="_subscript-31"><italic id="_italic-63">r</italic></sub><italic id="_italic-64"> = C</italic><sub id="_subscript-32"><italic id="_italic-65">min</italic></sub><italic id="_italic-66">/C</italic><sub id="_subscript-33"><italic id="_italic-67">max</italic></sub>(4)</p>
          <p id="_paragraph-35"><italic id="_italic-68">C</italic><sub id="_subscript-34"><italic id="_italic-69">r</italic></sub> =  heat-capacity-rate ratio, dimensionless (0 ≤ C<sub id="_subscript-35">r</sub> ≤ 1)</p>
          <p id="paragraph-889ffde05ceaf2c91fd5ee1274324200">
            <bold id="bold-d7f2d8968a764050868ade59c001c201">3.2 Local rate equation and the LMTD</bold>
          </p>
          <p id="_paragraph-36">Over a differential element of surface dA the local rate equation is</p>
          <p id="_paragraph-37"><italic id="_italic-70">dQ = U (T</italic><sub id="_subscript-36"><italic id="_italic-71">h</italic></sub><italic id="_italic-72"> − T</italic><sub id="_subscript-37"><italic id="_italic-73">c</italic></sub><italic id="_italic-74">) dA = U </italic><italic id="_italic-75">Δ</italic><italic id="_italic-76">T dA</italic>(5)</p>
          <p id="_paragraph-38"><italic id="_italic-77">U</italic> =  overall heat-transfer coefficient, W m⁻² K⁻¹</p>
          <p id="_paragraph-39"><italic id="_italic-78">ΔT</italic> =  local temperature difference between the streams, K</p>
          <p id="_paragraph-40"><italic id="_italic-79">A</italic> =  heat-transfer surface area, m²</p>
          <p id="_paragraph-41">Differentiating ΔT = T<sub id="_subscript-38">h</sub> − T<sub id="_subscript-39">c</sub> along the surface and using the differential forms of Eqs. (1)– (2) for counterflow gives d(ΔT) = −dQ (1/C<sub id="_subscript-40">h</sub> − 1/C<sub id="_subscript-41">c</sub>). Substituting dQ from Eq. (5) yields d(ΔT)/ΔT = −U(1/C<sub id="_subscript-42">h</sub> − 1/C<sub id="_subscript-43">c</sub>) dA, which integrates over the whole surface to . Eliminating the heat-capacity rates with Eqs. (1)– (2), and rearranging gives the LMTD result:</p>
          <p id="_paragraph-42"><italic id="_italic-80">Q = U A ΔT</italic><sub id="_subscript-44"><italic id="_italic-81">lm</italic></sub>(6)</p>
          <p id="_paragraph-43">(7)</p>
          <p id="_paragraph-44"><italic id="_italic-82">ΔT</italic><sub id="_subscript-45"><italic id="_italic-83">lm</italic></sub> = logarithmic mean temperature difference, K</p>
          <p id="_paragraph-45"><italic id="_italic-84">,</italic>= terminal temperature differences; for counterflow  and <italic id="_italic-85">ΔT</italic><sub id="_subscript-46"><italic id="_italic-86">2</italic></sub><italic id="_italic-87"> = T</italic><sub id="_subscript-47"><italic id="_italic-88">h,o</italic></sub><italic id="_italic-89"> − T</italic><sub id="_subscript-48"><italic id="_italic-90">c,i</italic></sub>, K</p>
          <p id="_paragraph-46">Equation (6) is exact for a constant overall coefficient and constant heat-capacity rates. It is the natural form when all four terminal temperatures are known and the area is required. When an installed exchanger fouls, however, the coefficient falls and the outlet temperatures become unknowns, so the effectiveness–NTU form of Section 3.4 is preferred; the two are algebraically equivalent.</p>
          <p id="paragraph-070d0171645e5e3989044f8fc2d8eaa8">
            <bold id="bold-c293dd2b48fc4e10c534296be5a7cf8b">3.3 Overall coefficient and the fouling resistance</bold>
          </p>
          <p id="_paragraph-47">Adding the series thermal resistances of the two convective films, the tube wall and the fouling deposits, and referring them to the reference (outer) surface, the clean overall coefficient is</p>
          <p id="_paragraph-48"><italic id="_italic-91">1/U</italic><sub id="_subscript-49"><italic id="_italic-92">c</italic></sub><italic id="_italic-93"> = 1/h</italic><sub id="_subscript-50"><italic id="_italic-94">h</italic></sub><italic id="_italic-95"> + R</italic><sub id="_subscript-51"><italic id="_italic-96">w</italic></sub><italic id="_italic-97"> + 1/h</italic><sub id="_subscript-52"><italic id="_italic-98">c</italic></sub><italic id="_italic-99">, </italic>(8–9)</p>
          <p id="_paragraph-49"><italic id="_italic-100">U</italic><sub id="_subscript-53"><italic id="_italic-101">c</italic></sub> = clean overall heat-transfer coefficient, W m⁻² K⁻¹</p>
          <p id="_paragraph-50"><italic id="_italic-102">h</italic><sub id="_subscript-54"><italic id="_italic-103">h</italic></sub><italic id="_italic-104">, h</italic><sub id="_subscript-55"><italic id="_italic-105">c</italic></sub> = hot and cold side film coefficients, W m⁻² K⁻¹</p>
          <p id="_paragraph-51"><italic id="_italic-106">R</italic><sub id="_subscript-56"><italic id="_italic-107">w</italic></sub> = wall conduction resistance, m² K W⁻¹</p>
          <p id="_paragraph-52"><italic id="_italic-108">, k</italic><sub id="_subscript-57"><italic id="_italic-109">w</italic></sub> = wall thickness (m) and thermal conductivity (W m⁻¹ K⁻¹)</p>
          <p id="_paragraph-53">Fouling adds a single lumped resistance R<sub id="_subscript-58">f</sub> in series (A6), so the fouled coefficient is</p>
          <p id="_paragraph-54"><italic id="_italic-110">1/U</italic><sub id="_subscript-59"><italic id="_italic-111">f</italic></sub><italic id="_italic-112"> = 1/U</italic><sub id="_subscript-60"><italic id="_italic-113">c</italic></sub><italic id="_italic-114"> + R</italic><sub id="_subscript-61"><italic id="_italic-115">f</italic></sub><italic id="_italic-116">⇒</italic><italic id="_italic-117"> U</italic><sub id="_subscript-62"><italic id="_italic-118">f</italic></sub><italic id="_italic-119"> = U</italic><sub id="_subscript-63"><italic id="_italic-120">c</italic></sub><italic id="_italic-121"> / (1 + U</italic><sub id="_subscript-64"><italic id="_italic-122">c</italic></sub><italic id="_italic-123"> R</italic><sub id="_subscript-65"><italic id="_italic-124">f</italic></sub><italic id="_italic-125">)</italic>(10–11)</p>
          <p id="_paragraph-55"><italic id="_italic-126">U</italic><sub id="_subscript-66"><italic id="_italic-127">f</italic></sub> = fouled overall coefficient, W m⁻² K⁻¹</p>
          <p id="_paragraph-56"><italic id="_italic-128">R</italic><sub id="_subscript-67"><italic id="_italic-129">f</italic></sub> = fouling (thermal) resistance referred to A, m² K W⁻¹</p>
          <p id="_paragraph-57">The group U<sub id="_subscript-68">f</sub>/U<sub id="_subscript-69">c</sub> = 1/ (1 + U<sub id="_subscript-70">c</sub> R<sub id="_subscript-71">f</sub>) is the cleanliness factor. Equation (11) already shows the essential non-linearity of fouling: because the fouling resistance is added to 1/U rather than to U, the same increment of R<sub id="_subscript-72">f</sub> costs more duty when the clean coefficient is high than when it is low.</p>
          <p id="paragraph-01b3d3eeaa5c9e62557183ddaf5f1079">
            <bold id="bold-18b0dd511b0d4ca76bea5b4c4626d24e">3.4 Effectiveness–NTU formulation</bold>
          </p>
          <p id="_paragraph-58">The thermodynamic maximum duty is that of an infinitely long counterflow exchanger, in which the stream of smaller heat-capacity rate is brought to the inlet temperature of the other stream:</p>
          <p id="_paragraph-59"><italic id="_italic-130">Q</italic><sub id="_subscript-73"><italic id="_italic-131">max</italic></sub><italic id="_italic-132"> = C</italic><sub id="_subscript-74"><italic id="_italic-133">min</italic></sub><italic id="_italic-134"> (T</italic><sub id="_subscript-75"><italic id="_italic-135">h,i</italic></sub><italic id="_italic-136"> − T</italic><sub id="_subscript-76"><italic id="_italic-137">c,i</italic></sub><italic id="_italic-138">)</italic>(12)</p>
          <p id="_paragraph-60">The effectiveness and the number of transfer units are defined by</p>
          <p id="_paragraph-61"><italic id="_italic-139">ε = Q / Q</italic><sub id="_subscript-77"><italic id="_italic-140">max</italic></sub><italic id="_italic-141">,     NTU = U A / C</italic><sub id="_subscript-78"><italic id="_italic-142">min</italic></sub>(13–14)</p>
          <p id="_paragraph-62"><italic id="_italic-143">ε</italic> =  thermal effectiveness, dimensionless (0 ≤ ε ≤ 1)</p>
          <p id="_paragraph-63"><italic id="_italic-144">NTU</italic> =  number of transfer units, dimensionless</p>
          <p id="_paragraph-64">Starting from the integrated LMTD relation  and expressing the terminal differences in terms of ε and C<sub id="_subscript-79">r</sub>, the standard counterflow effectiveness relation follows:</p>
          <p id="_paragraph-65"><italic id="_italic-145">ε = [1 − exp(−NTU(1 − C</italic><sub id="_subscript-80"><italic id="_italic-146">r</italic></sub><italic id="_italic-147">))] / [1 − C</italic><sub id="_subscript-81"><italic id="_italic-148">r</italic></sub><italic id="_italic-149"> exp(−NTU(1 − C</italic><sub id="_subscript-82"><italic id="_italic-150">r</italic></sub><italic id="_italic-151">))] ,   C</italic><sub id="_subscript-83"><italic id="_italic-152">r</italic></sub><italic id="_italic-153"> &lt; 1</italic>(15)</p>
          <p id="_paragraph-66"><italic id="_italic-154">ε = NTU / (1 + NTU),   C</italic><sub id="_subscript-84"><italic id="_italic-155">r</italic></sub><italic id="_italic-156"> = 1</italic>(16)</p>
          <p id="_paragraph-67">Once the effectiveness is known, the duty follows from Eq. (13) and the outlet temperatures from the energy balances (1)–(2):</p>
          <p id="_paragraph-68"><italic id="_italic-157">T</italic><sub id="_subscript-85"><italic id="_italic-158">h,o</italic></sub><italic id="_italic-159"> = T</italic><sub id="_subscript-86"><italic id="_italic-160">h,i</italic></sub><italic id="_italic-161"> − Q/C</italic><sub id="_subscript-87"><italic id="_italic-162">h</italic></sub><italic id="_italic-163"> ,     T</italic><sub id="_subscript-88"><italic id="_italic-164">c,o</italic></sub><italic id="_italic-165"> = T</italic><sub id="_subscript-89"><italic id="_italic-166">c,i</italic></sub><italic id="_italic-167"> + Q/C</italic><sub id="_subscript-90"><italic id="_italic-168">c</italic></sub>(17)</p>
          <p id="_paragraph-69">TheEqs. (15)– (17)are the thermal engine of the model. Given the instantaneous overall coefficient U<sub id="_subscript-91">f</sub>(t) from Eq. (11), they return the effectiveness, the duty and both outlet temperatures without iteration. Since NTU is directly proportional to U, any reduction in U<sub id="_subscript-92">f</sub>(t) caused by fouling decreases the heat exchanger effectiveness and, for fixed inlet conditions and heat-capacity rates, results in a corresponding reduction in the heat-transfer duty.</p>
          <p id="paragraph-3b7db4e58d501306c2a962dab4b490d9">
            <bold id="bold-f4f66f28d76c01d7749a7a00c7bfa89c">3.5 Asymptotic fouling law with velocity and temperature dependence</bold>
          </p>
          <p id="_paragraph-70">Following the deposition–removal picture, the net rate of growth of the fouling resistance is</p>
          <p id="_paragraph-71">(18)</p>
          <p id="_paragraph-72"> = deposition rate of fouling resistance, m² K W⁻¹ s⁻¹</p>
          <p id="_paragraph-73"> = removal rate of fouling resistance, m² K W⁻¹ s⁻¹</p>
          <p id="_paragraph-74">Adopting the Kern–Seaton hypothesis that removal is proportional to the amount of deposit present, , while deposition is set by the local conditions, , Eq becomes a linear first-order ordinary differential equation:</p>
          <p id="_paragraph-75"><italic id="_italic-169">dR</italic><sub id="_subscript-93"><italic id="_italic-170">f</italic></sub><italic id="_italic-171">/dt = a</italic><sub id="_subscript-94"><italic id="_italic-172">d</italic></sub><italic id="_italic-173"> − b</italic><sub id="_subscript-95"><italic id="_italic-174">r</italic></sub><italic id="_italic-175"> R</italic><sub id="_subscript-96"><italic id="_italic-176">f</italic></sub>(19)</p>
          <p id="_paragraph-76">With the clean initial condition R<sub id="_subscript-97">f</sub>(0) = 0 the solution is the classical asymptotic curve</p>
          <p id="_paragraph-77"><italic id="_italic-177">R</italic><sub id="_subscript-98"><italic id="_italic-178">f</italic></sub><italic id="_italic-179">(t) = R</italic><sub id="_subscript-99"><italic id="_italic-180">f</italic></sub><sup id="_superscript-2"><italic id="_italic-181">*</italic></sup><italic id="_italic-182"> [1 − exp(−t/τ)]</italic>(20)</p>
          <p id="_paragraph-78"><italic id="_italic-183">R</italic><sub id="_subscript-100"><italic id="_italic-184">f</italic></sub><sup id="_superscript-3"><italic id="_italic-185">*</italic></sup><italic id="_italic-186"> = a</italic><sub id="_subscript-101"><italic id="_italic-187">d</italic></sub><italic id="_italic-188"> / b</italic><sub id="_subscript-102"><italic id="_italic-189">r</italic></sub><italic id="_italic-190">,    τ = 1 / b</italic><sub id="_subscript-103"><italic id="_italic-191">r</italic></sub>(21)</p>
          <p id="_paragraph-79"><italic id="_italic-192">a</italic><sub id="_subscript-104"><italic id="_italic-193">d</italic></sub> =  deposition coefficient, m² K W⁻¹ s⁻¹</p>
          <p id="_paragraph-80"><italic id="_italic-194">b</italic><sub id="_subscript-105"><italic id="_italic-195">r</italic></sub> =  removal-rate coefficient, s⁻¹</p>
          <p id="_paragraph-81"><italic id="_italic-196">R</italic><sub id="_subscript-106"><italic id="_italic-197">f</italic></sub><sup id="_superscript-4"><italic id="_italic-198">*</italic></sup> =  asymptotic fouling resistance, m² K W⁻¹</p>
          <p id="_paragraph-82"><italic id="_italic-199">τ</italic> =  fouling time constant, s</p>
          <p id="_paragraph-83">The mechanistic content is placed in the two coefficients. Deposition is taken as an Arrhenius function of the film (deposition-surface) temperature and a power law in the mean velocity, reflecting reaction- or mass-transfer-controlled attachment; removal is taken proportional to the wall shear stress, which for turbulent flow scales approximately as the square of the velocity:</p>
          <p id="_paragraph-84"><italic id="_italic-200">a</italic><sub id="_subscript-107"><italic id="_italic-201">d</italic></sub><italic id="_italic-202"> = A</italic><sub id="_subscript-108"><italic id="_italic-203">d</italic></sub><italic id="_italic-204"> u</italic><sup id="_superscript-5"><italic id="_italic-205">m</italic></sup><italic id="_italic-206"> exp(−E</italic><sub id="_subscript-109"><italic id="_italic-207">a</italic></sub><italic id="_italic-208"> / R</italic><sub id="_subscript-110"><italic id="_italic-209">g</italic></sub><italic id="_italic-210"> T</italic><sub id="_subscript-111"><italic id="_italic-211">f</italic></sub><italic id="_italic-212">)</italic>(22)</p>
          <p id="_paragraph-85"><italic id="_italic-213">b</italic><sub id="_subscript-112"><italic id="_italic-214">r</italic></sub><italic id="_italic-215"> = A</italic><sub id="_subscript-113"><italic id="_italic-216">r</italic></sub><italic id="_italic-217"> u</italic><sup id="_superscript-6"><italic id="_italic-218">n</italic></sup>(23)</p>
          <p id="_paragraph-86"><italic id="_italic-219">A</italic><sub id="_subscript-114"><italic id="_italic-220">d</italic></sub> =  deposition pre-factor, m² K W⁻¹ s⁻¹ (m s⁻¹)⁻ᵐ</p>
          <p id="_paragraph-87"><italic id="_italic-221">A</italic><sub id="_subscript-115"><italic id="_italic-222">r</italic></sub> =  removal pre-factor, s⁻¹ (m s⁻¹)⁻ⁿ</p>
          <p id="_paragraph-88"><italic id="_italic-223">u</italic> =  mean tube (fouling-side) velocity, m s⁻¹</p>
          <p id="_paragraph-89"><italic id="_italic-224">m, n</italic> =  velocity exponents of deposition and removal, dimensionless (here m ≈ 0.4, n ≈ 2)</p>
          <p id="_paragraph-90"><italic id="_italic-225">E</italic><sub id="_subscript-116"><italic id="_italic-226">a</italic></sub> =  activation energy of the deposition reaction, J mol⁻¹</p>
          <p id="_paragraph-91"><italic id="_italic-227">R</italic><sub id="_subscript-117"><italic id="_italic-228">g</italic></sub> =  universal gas constant, 8.314 J mol⁻¹ K⁻¹</p>
          <p id="_paragraph-92"><italic id="_italic-229">T</italic><sub id="_subscript-118"><italic id="_italic-230">f</italic></sub> =  film (deposition-surface) temperature, K</p>
          <p id="_paragraph-93">Substituting Eqs into Eq gives explicit expressions for the plateau and the time constant:</p>
          <p id="_paragraph-94"><italic id="_italic-231">R</italic><sub id="_subscript-119"><italic id="_italic-232">f</italic></sub><sup id="_superscript-7"><italic id="_italic-233">*</italic></sup><italic id="_italic-234">(u, T</italic><sub id="_subscript-120"><italic id="_italic-235">f</italic></sub><italic id="_italic-236">) = (A</italic><sub id="_subscript-121"><italic id="_italic-237">d</italic></sub><italic id="_italic-238">/A</italic><sub id="_subscript-122"><italic id="_italic-239">r</italic></sub><italic id="_italic-240">) u</italic><sup id="_superscript-8"><italic id="_italic-241">m-n</italic></sup><italic id="_italic-242"> exp(−E</italic><sub id="_subscript-123"><italic id="_italic-243">a</italic></sub><italic id="_italic-244"> / R</italic><sub id="_subscript-124"><italic id="_italic-245">g</italic></sub><italic id="_italic-246"> T</italic><sub id="_subscript-125"><italic id="_italic-247">f</italic></sub><italic id="_italic-248">)</italic>(24)</p>
          <p id="_paragraph-95"><italic id="_italic-249">τ(u) = 1 / (A</italic><sub id="_subscript-126"><italic id="_italic-250">r</italic></sub><italic id="_italic-251"> u</italic><sup id="_superscript-9"><italic id="_italic-252">n</italic></sup><italic id="_italic-253">)</italic>(25)</p>
          <p id="_paragraph-96">For computation it is convenient to normalize Eq to a reference velocity u₀ and reference film temperature T<sub id="_subscript-127">f,ref</sub> at which the asymptotic resistance is R<sub id="_subscript-128">f,ref</sub><sup id="_superscript-10">*</sup>:</p>
          <p id="_paragraph-97"><italic id="_italic-254">R</italic><sub id="_subscript-129"><italic id="_italic-255">f</italic></sub><sup id="_superscript-11"><italic id="_italic-256">*</italic></sup><italic id="_italic-257">(u, T</italic><sub id="_subscript-130"><italic id="_italic-258">f</italic></sub><italic id="_italic-259">) = R</italic><sub id="_subscript-131"><italic id="_italic-260">f,ref</italic></sub><sup id="_superscript-12"><italic id="_italic-261">*</italic></sup><italic id="_italic-262"> (u/u</italic><sub id="_subscript-132"><italic id="_italic-263">0</italic></sub><italic id="_italic-264">)</italic><sup id="_superscript-13"><italic id="_italic-265">m-n</italic></sup><italic id="_italic-266"> exp[ (E</italic><sub id="_subscript-133"><italic id="_italic-267">a</italic></sub><italic id="_italic-268">/R</italic><sub id="_subscript-134"><italic id="_italic-269">g</italic></sub><italic id="_italic-270">)(1/T</italic><sub id="_subscript-135"><italic id="_italic-271">f,ref</italic></sub><italic id="_italic-272"> − 1/T</italic><sub id="_subscript-136"><italic id="_italic-273">f</italic></sub><italic id="_italic-274">) ]</italic>(26)</p>
          <p id="paragraph-160b71477dc3a29365b988d2ce3f3818">
            <bold id="bold-4ca9936aa1289fe3c9e68af8c894b4ec">3.6 Film-temperature closure</bold>
          </p>
          <p id="_paragraph-98">The fouling law needs the temperature at the deposition surface, which links it back to the thermal state. Splitting the temperature drop across the series resistances, the film temperature on the fouling side is estimated from the current overall coefficient and the fouling-side film coefficient:</p>
          <p id="_paragraph-99"><italic id="_italic-275">T</italic><sub id="_subscript-137"><italic id="_italic-276">f</italic></sub><italic id="_italic-277"> = T</italic><sub id="_subscript-138"><italic id="_italic-278">h,avg</italic></sub><italic id="_italic-279"> − (U/h</italic><sub id="_subscript-139"><italic id="_italic-280">h</italic></sub><italic id="_italic-281">)(T</italic><sub id="_subscript-140"><italic id="_italic-282">h,avg</italic></sub><italic id="_italic-283"> − T</italic><sub id="_subscript-141"><italic id="_italic-284">c,avg</italic></sub><italic id="_italic-285">)</italic>(27)</p>
          <p id="_paragraph-100"><italic id="_italic-286">T</italic><sub id="_subscript-142"><italic id="_italic-287">h,avg</italic></sub> =  arithmetic mean hot-stream temperature, (T<sub id="_subscript-143">h,i</sub>+T<sub id="_subscript-144">h,o</sub>)/2, K</p>
          <p id="_paragraph-101"><italic id="_italic-288">T</italic><sub id="_subscript-145"><italic id="_italic-289">c,avg</italic></sub> =  arithmetic mean cold-stream temperature, (T<sub id="_subscript-146">c,i</sub>+T<sub id="_subscript-147">c,o</sub>)/2, K</p>
          <p id="_paragraph-102">As fouling lowers U, the ratio U/h<sub id="_subscript-148">h</sub> falls and T<sub id="_subscript-149">f</sub> rises toward the hot-stream temperature; through the Arrhenius factor of Eq this accelerates further deposition. Equation is the closure that makes temperature an active, coupled variable rather than a fixed parameter.</p>
          <p id="paragraph-7d8feaf21585ed795ef2593ffc91aa3c">
            <bold id="bold-a790ee82bc55d549a1d905df6cc726e6">3.7 Coupled quasi-steady algorithm</bold>
          </p>
          <p id="_paragraph-103">Equations (11), (13)–(17), (19), (23), (26) and (27) form a closed set. On the slow fouling clock, the thermal relations are algebraic and the only differential equation is Eq for Rf. This implies that we solve a single ODE and follow it with an algebraic thermal update at each step.</p>
          <list list-type="order" id="list-d679ff71a84dc967ff5c5dc7ba03397c">
            <list-item>
              <p>Evaluate Uf from Eq. (11).</p>
            </list-item>
            <list-item>
              <p>Calculate NTU (14), ε (15)–(16), Q (13) and T−outlet from (17).</p>
            </list-item>
            <list-item>
              <p>First you will be evaluating the film temperature Tf (27), then Rf*(26) and finally br (23).</p>
            </list-item>
            <list-item>
              <p>Form the rate from Eq dRf/dt = br (Rf* − Rf) (19) and advance Rf in time.</p>
            </list-item>
          </list>
          <p id="_paragraph-104">For this reason, the method is explicit and requires neither matrix inversion nor iterations of nested loops which renders it cheap enough to be used in repetitions on-line.</p>
          <p id="paragraph-9dd56159f806fb27c7e40e50e8fd5437">
            <bold id="bold-e4749922dcfaba2a0cd89737ccb1197e">3.8 The fouling-degradation number</bold>
          </p>
          <p id="_paragraph-105">The loss in performance is asymptotic and dominated by a single dimensionless group, the ratio of the clean coefficient to the plateau resistance,</p>
          <p id="_paragraph-106"><italic id="_italic-290">Θ = U</italic><sub id="_subscript-150"><italic id="_italic-291">c</italic></sub><italic id="_italic-292"> R</italic><sub id="_subscript-151"><italic id="_italic-293">f</italic></sub><italic id="_italic-294">*</italic>(28)</p>
          <p id="_paragraph-107"><italic id="_italic-295">Θ</italic> =  fouling-degradation number, dimensionless</p>
          <p id="_paragraph-108">From Eq. (11) the asymptotic cleanliness factor and the asymptotic NTU ratio are U<sub id="_subscript-152">f</sub><sup id="_superscript-14">*</sup>/U<sub id="_subscript-153">c</sub> = NTU<sub id="_subscript-154">∞</sub>/NTU<sub id="_subscript-155">c</sub> = 1/(1 + Θ). Group Θ is a Biot-like number that compares deposits resistance versus clean holistic resistance, as it collapses the family of degradation curves and gives compact design criterion; targeting intolerable NTU loss directly translates into an upper-bound on Θ.</p>
          <p id="paragraph-e5b59f2727dff5cba24af149a9bdd227">
            <bold id="bold-9367366989a59d62b26460dcf9086285">3.9 Closed-form sensitivity coefficients</bold>
          </p>
          <p id="_paragraph-109">A key advantage of an analytical model is we can write its sensitivities in closed form. Using the normalized sensitivity S<sub id="_subscript-156">x</sub><sup id="_superscript-15">Y</sup> = (x/Y)(∂Y/∂x), differentiation of Eq. (15) gives, with β = NTU(1 − C<sub id="_subscript-157">r</sub>),</p>
          <p id="_paragraph-110"><italic id="_italic-296">∂ε/∂NTU = (1 − C</italic><sub id="_subscript-158"><italic id="_italic-297">r</italic></sub><italic id="_italic-298">)² exp(−β) / [1 − C</italic><sub id="_subscript-159"><italic id="_italic-299">r</italic></sub><italic id="_italic-300"> exp(−β)]²</italic>(29)</p>
          <p id="_paragraph-111">(30)</p>
          <p id="_paragraph-112">The sensitivity of the overall coefficient to the fouling resistance follows from Eq. (11):</p>
          <p id="_paragraph-113"><italic id="_italic-301">S</italic><sub id="_subscript-160"><italic id="_italic-302">Rf</italic></sub><sup id="_superscript-16"><italic id="_italic-303">U</italic></sup><italic id="_italic-304"> = (R</italic><sub id="_subscript-161"><italic id="_italic-305">f</italic></sub><italic id="_italic-306">/U)(∂U/∂R</italic><sub id="_subscript-162"><italic id="_italic-307">f</italic></sub><italic id="_italic-308">) = − U</italic><sub id="_subscript-163"><italic id="_italic-309">c</italic></sub><italic id="_italic-310"> R</italic><sub id="_subscript-164"><italic id="_italic-311">f</italic></sub><italic id="_italic-312"> / (1 + U</italic><sub id="_subscript-165"><italic id="_italic-313">c</italic></sub><italic id="_italic-314"> R</italic><sub id="_subscript-166"><italic id="_italic-315">f</italic></sub><italic id="_italic-316">) = −Θ/(1+Θ)</italic>(31)</p>
          <p id="_paragraph-114">Hence there are two exact identities: because the duty is a function of inlet temperature difference at constant effectiveness, and NTU is proportional to U</p>
          <p id="_paragraph-115"><italic id="_italic-317">S</italic><sub id="_subscript-167"><italic id="_italic-318">ΔTin</italic></sub><sup id="_superscript-17"><italic id="_italic-319">Q</italic></sup><italic id="_italic-320"> = 1,</italic> (32-33)</p>
          <p id="_paragraph-116">By application of the chain rule, we obtain the sensitivity of the duty with respect to the flow rate on minimum capacity stream. Since C<sub id="_subscript-168">min</sub> ∝ ṁ and the film coefficient scales as h<sub id="_subscript-169">h</sub> ∝ u<sup id="_superscript-18">0.8</sup> ∝ ṁ<sup id="_superscript-19">0.8</sup>, so that S<sub id="_subscript-170">ṁ</sub><sup id="_superscript-20">U</sup> = 0.8 U/h<sub id="_subscript-171">h</sub> and S<sub id="_subscript-172">ṁ</sub><sup id="_superscript-21">NTU</sup> = S<sub id="_subscript-173">ṁ</sub><sup id="_superscript-22">U</sup> − 1,</p>
          <p id="_paragraph-117"><italic id="_italic-321">S</italic><sub id="_subscript-174"><italic id="_italic-322">ṁ</italic></sub><sup id="_superscript-23"><italic id="_italic-323">Q</italic></sup><italic id="_italic-324"> = 1 + </italic><italic id="_italic-325">(S</italic><sub id="_subscript-175"><italic id="_italic-326">ṁ</italic></sub><sup id="_superscript-24"><italic id="_italic-327">U</italic></sup><italic id="_italic-328"> − 1)</italic>(34)</p>
          <p id="_paragraph-118">Equation (34) describes a behavior that is genuinely non-intuitive: increased flow rate raises duty (numerator 1), but lowered NTU (the negative term), hence the overall gain is sub-proportional. Section 6.4 lists the corresponding numerical values of all these coefficients for the case study.</p>
          <p id="paragraph-1f1605d9aee87d166a26a2a1762e138e">
            <bold id="bold-660635e45f471a981d3adcebfd5cf16e">3.10 Uncertainty propagation</bold>
          </p>
          <p id="_paragraph-119">Because the model is analytical, measurement uncertainties propagate to the predicted quantities in closed form. From Eq. (1), Q = ṁ<sub id="_subscript-176">h</sub> c<sub id="_subscript-177">p,h</sub>(T<sub id="_subscript-178">h,i</sub> − T<sub id="_subscript-179">h,o</sub>), the relative uncertainty of the duty is</p>
          <p id="_paragraph-120"><italic id="_italic-329">(u</italic><sub id="_subscript-180"><italic id="_italic-330">Q</italic></sub><italic id="_italic-331">/Q)² = (u</italic><sub id="_subscript-181"><italic id="_italic-332">ṁ</italic></sub><italic id="_italic-333">/ṁ)² + (u</italic><sub id="_subscript-182"><italic id="_italic-334">cp</italic></sub><italic id="_italic-335">/c</italic><sub id="_subscript-183"><italic id="_italic-336">p</italic></sub><italic id="_italic-337">)² + 2 (u</italic><sub id="_subscript-184"><italic id="_italic-338">T</italic></sub><italic id="_italic-339">/ΔT</italic><sub id="_subscript-185"><italic id="_italic-340">h</italic></sub><italic id="_italic-341">)²</italic>(35)</p>
          <p id="_paragraph-121"><italic id="_italic-342">u</italic><sub id="_subscript-186"><italic id="_italic-343">Q</italic></sub><italic id="_italic-344">, u</italic><sub id="_subscript-187"><italic id="_italic-345">ṁ</italic></sub><italic id="_italic-346">, u</italic><sub id="_subscript-188"><italic id="_italic-347">cp</italic></sub><italic id="_italic-348">, u</italic><sub id="_subscript-189"><italic id="_italic-349">T</italic></sub> =  standard uncertainties of duty, mass flow, specific heat and temperature</p>
          <p id="_paragraph-122"><italic id="_italic-350">ΔT</italic><sub id="_subscript-190"><italic id="_italic-351">h</italic></sub> =  hot-stream temperature change, T<sub id="_subscript-191">h,i</sub> − T<sub id="_subscript-192">h,o</sub>, K</p>
          <p id="_paragraph-123">When the overall coefficient is inferred from measured duty and temperatures through U = Q/(A ΔT<sub id="_subscript-193">lm</sub>), the fouling resistance obtained from Eq. (10), R<sub id="_subscript-194">f</sub> = 1/U<sub id="_subscript-195">f</sub> − 1/U<sub id="_subscript-196">c</sub>, carries an uncertainty</p>
          <p id="_paragraph-124"><italic id="_italic-352">u</italic><sub id="_subscript-197"><italic id="_italic-353">Rf</italic></sub><italic id="_italic-354"> = u</italic><sub id="_subscript-198"><italic id="_italic-355">U</italic></sub><italic id="_italic-356"> / U</italic><sub id="_subscript-199"><italic id="_italic-357">f</italic></sub><italic id="_italic-358">²</italic>(36–37)</p>
          <p id="_paragraph-125">Equation (35) shows why a close temperature approach is dangerous for monitoring: as ΔT<sub id="_subscript-200">h</sub> shrinks, the term 2(u<sub id="_subscript-201">T</sub>/ΔT<sub id="_subscript-202">h</sub>)² grows, and the same absolute temperature error produces a much larger relative error in the inferred duty and, through Eq. (37), in the fouling resistance. This is quantified for the case study in Section 6.5.</p>
        </sec>
      </sec>
    </sec>
    <sec id="sec-4">
      <title>Methodology</title>
      <p id="paragraph-5f34f9b339cc0814071404b943e22952">
        <bold id="bold-59a7d392261a6d92c14fcd9fc764e0fa">4.1 Numerical implementation</bold>
      </p>
      <p id="_paragraph-126">The model was implemented from scratch in Python 3 using only the NumPy numerical library; no commercial process simulator, computational-fluid-dynamics package or symbolic-algebra tool was used at any stage. The single ordinary differential equation for the fouling resistance Eq was integrated with the classical fourth-order Runge–Kutta scheme using a fixed step of 0.25 day over a 360-day horizon. At every step the thermal update (Section 3.7) was evaluated algebraically, so the whole calculation is explicit and non-iterative. Step-size halving changed the computed asymptotic resistance by less than 0.01%, confirming that the reported results are step-independent. The complete calculation for one operating case runs in well under a second on an ordinary desktop, which is the property that makes the model suitable for embedding in a monitoring or scheduling loop.</p>
      <p id="paragraph-e8e77b450026ac67d4941aaeead20670">
        <bold id="bold-23d19b18bc6ab7221ca84961e538b2fa">4.2 Illustrative case study</bold>
      </p>
      <p id="_paragraph-127">To exercise the model, we use a counterflow shell-and-tube exchanger in which a hot process stream is cooled by water. However, the operating point and physical properties are characteristic of a light-hydrocarbon cooler; they are internally consistent but illustrative, they were chosen to show the model rather than to reflect a specific measured unit. All derived quantities duty, effectiveness, outlet temperatures, fouling resistance are computed from the governing equations of Section 3 and are therefore thermodynamically consistent with the stated inputs. Figure 1 shows the arrangement and Table 1 lists the input parameters.</p>
      <fig id="fig2">
        <label>Figure 2</label>
        <caption>
          <p id="_paragraph-128"/>
        </caption>
        <graphic id="_graphic-2" mimetype="image" mime-subtype="png" xlink:href="image2.png"/>
      </fig>
      <p id="_paragraph-129">
        <bold id="_bold-22">Figure 1. </bold>
        <bold id="_bold-23">Counterflow shell-and-tube arrangement used in the case study. </bold>
      </p>
      <p id="_paragraph-130">The hot stream (shell side) and cold stream (tube side) flow in opposite directions; a fouling deposit of time-dependent resistance R<sub id="_subscript-203">f</sub>(t) grows on the heat-transfer surface and adds in series with the clean resistance, so that 1/U<sub id="_subscript-204">f</sub> = 1/U<sub id="_subscript-205">c</sub> + R<sub id="_subscript-206">f</sub>(t).</p>
      <p id="_paragraph-131">
        <bold id="_bold-24">Table 1.</bold>
        <bold id="_bold-25">Input parameters of the illustrative counterflow case study (illustrative, thermodynamically consistent).</bold>
      </p>
      <fig id="fig3">
        <label>Figure 3</label>
        <caption>
          <p id="_paragraph-132"/>
        </caption>
        <graphic id="_graphic-3" mimetype="image" mime-subtype="png" xlink:href="image3.png"/>
      </fig>
      <p id="paragraph-fae54b8ff48aeea69714c5fb6bd355bf">
        <bold id="bold-35ff78b1aae84eeeb10dbd1004e894f1">4.3 Clean design point</bold>
      </p>
      <p id="_paragraph-133">Evaluating Eqs gives C<sub id="_subscript-207">h</sub> = 26.4 kW K⁻¹ and C<sub id="_subscript-208">c</sub> = 83.6 kW K⁻¹, so the hot stream carries the minimum heat-capacity rate, C<sub id="_subscript-209">min</sub> = 26.4 kW K⁻¹, and C<sub id="_subscript-210">r</sub> = 0.316. With the clean coefficient U<sub id="_subscript-211">c</sub> = 464 W m⁻² K⁻¹ from Eqs, the clean design point follows from Eqs and is summarized in Table 2. These values are the baseline against which the fouled states of Section 6 are measured.</p>
      <p id="_paragraph-134">
        <bold id="_bold-26">Table 2.</bold>
        <bold id="_bold-27">Calculation of clean design point </bold>
        <bold id="_bold-28">result </bold>
        <bold id="_bold-29">based on equations</bold>
        <bold id="_bold-30">.</bold>
      </p>
      <fig id="fig4">
        <label>Figure 4</label>
        <caption>
          <p id="_paragraph-135"/>
        </caption>
        <graphic id="_graphic-4" mimetype="image" mime-subtype="png" xlink:href="image4.png"/>
      </fig>
      <sec id="heading-4992a445b74c20efb8d0bfcda6c7acf8">
        <title>5. Model Validation</title>
        <p id="_paragraph-136">Since the case-study data are not measured, but rather illustrative, validation in this context is showing that the implementation produces analytical limits consistent with self-consistent governing equations and qualitative trends identified through the literature of experiments. Three independent checks are reported.</p>
        <p id="paragraph-9d18ae72273b368e470f967bdf63f2ac">
          <bold id="bold-7140b7fc7a98081b9114ee7f3fe2bc51">5.1 Consistency of the ε–NTU and LMTD routes</bold>
        </p>
        <p id="_paragraph-137">Since the energy balance and local rate equation generate both ε–NTU and LMTD methods must return the same duty for identical conditions. The effectiveness was then computed using the following eq. The outlet temperatures to form one logarithmic-mean temperature difference and separate duty U A ΔT<sub id="_subscript-212">lm</sub>. As can be seen in Figure 2(a), the LMTD cross-check points meet the ε - NTU curve perfectly over the full range, verifying both their algebraic equivalence as well as implementation correctness.</p>
        <p id="paragraph-c3199613dff6ece9c0c0e38cbebe7271">
          <bold id="bold-1b259db35fbf4db086634e2d64401e8b">5.2 Verification of the fouling law</bold>
        </p>
        <p id="_paragraph-138">However, Eq. Exact solution of Eq. (19) is scenario in which the force homogeneously distributed along y direction 20). In Figure 2(b), the true trajectory, which evolves according to Eq. The frozen-temperature closed-form, The two curves have identical initial slope and time constant; they diverge only as the increasing temperature of the rising film in the coupled solution raises the plateau, just the positive feedback found in Section 3.5. The agreement in the early, temperature-independent regime confirms the integrator and controlled divergence at late times verifies that the temperature coupling functions as designed.</p>
        <fig id="fig5">
          <label>Figure 5</label>
          <caption>
            <p id="_paragraph-139"/>
          </caption>
          <graphic id="_graphic-5" mimetype="image" mime-subtype="png" xlink:href="image5.png"/>
        </fig>
        <p id="_paragraph-140">
          <bold id="_bold-31">Figure 2. </bold>
          <bold id="_bold-32">Model verification.</bold>
        </p>
        <p id="_paragraph-141"> (a) Effectiveness from the ε–NTU relation (line) and duty recomputed using the LMTD route (points); however, they are equal along this NTU range. (b) The tal in fouling resistance from the coupled Runge-Kutta solution (solid) and frozen-film-temperature closed form of Eq (dashed'; they agree at short times and diverge only when the coupled film temperature increases the plateau.</p>
        <p id="paragraph-ca2f031be11379b40e87c2aef5d52dd9">
          <bold id="bold-dff117df596f1e0351079fc34d15ea8c">5.3 Consistency with experimental trends</bold>
        </p>
        <p id="_paragraph-142">The model produces the main qualitative trends observed experimentally for fouling systems, beyond internal validation. In the first one, the decrease of asymptotic resistance is monotonic with an increase in speed (Eq. 24 with m &lt; n) which conform with long-standing observation that enhanced shear suppresses net deposition. Second, for n = 2 (removal exponent) the fouling time constant scales as u⁻², this trend matching the inverse-square reliance of time fouling on velocity that was previously reported for both water-side and crude-oil systems. Third, the Arrhenius dependence of the plateau on film temperature reproduces the accelerating effect of surface temperature that underlies the threshold behavior of Ebert and Panchal. The quantitative demonstration of these trends is given in Section 6.2 and 6.3. Finally, the energy balance is satisfied identically at every instant by construction, since the duty entering the cold stream equals that leaving the hot stream in Eqs.</p>
      </sec>
    </sec>
    <sec id="sec-6">
      <title>Results</title>
      <p id="paragraph-6795b1bcddc3b1ddd144349bb38c1002">
        <bold id="bold-78b07ab0e2ff89945655a5311bfdb3c3">6.1 Dynamic performance degradation at the design velocity</bold>
      </p>
      <p id="_paragraph-143">Integrating the coupled model at the design velocity produces the fouling trajectory of Figure 3 and the performance degradation of Figure 4. The fouling resistance rises from zero and approaches an asymptote of R<sub id="_subscript-213">f</sub><sup id="_superscript-25">*</sup> = 5.50 × 10⁻⁴ m² K W⁻¹ with a time constant of about 30 days; roughly three-time constants (three months) are needed before the deposit is effectively fully developed. The corresponding fouling-degradation number is Θ = U<sub id="_subscript-214">c</sub> R<sub id="_subscript-215">f</sub><sup id="_superscript-26">*</sup> = 0.255.</p>
      <fig id="fig6">
        <label>Figure 6</label>
        <caption>
          <p id="_paragraph-144"/>
        </caption>
        <graphic id="_graphic-6" mimetype="image" mime-subtype="png" xlink:href="image6.png"/>
      </fig>
      <p id="_paragraph-145">
        <bold id="_bold-33">Figure 3. </bold>
        <bold id="_bold-34">Asymptotic build-up of fouling resistance for three tube velocities.</bold>
      </p>
      <p id="_paragraph-146">Solid curves are the computed trajectories; dotted lines mark the predicted asymptotes R<sub id="_subscript-216">f</sub><sup id="_superscript-27">*</sup>. Higher velocity lowers the plateau and shortens the time constant simultaneously.</p>
      <p id="_paragraph-147">The consequences for performance are shown in Figure 4 and tabulated month by month in Table 3. Over the horizon the overall coefficient falls by 20.3% (from 464 to 370 W m⁻² K⁻¹), yet the effectiveness and the duty fall by only 10.7% (the duty from 2875 to 2567 kW). One of the most useful outputs of the model is this asymmetry. It occurs because the exchanger functions on the concave section of the ε–NTU curve: where effectiveness responds in less than sub-proportion to NTU; elasticity (Section 7.4), so a loss of NTU by 20% results in a duty drop attenuated by ~11%. For instance, an engineer who assumed that the fractional loss of coefficient is equal to the fractional loss in duty would be writing a thermal penalty almost two times too high.</p>
      <fig id="fig7">
        <label>Figure 7</label>
        <caption>
          <p id="_paragraph-148"/>
        </caption>
        <graphic id="_graphic-7" mimetype="image" mime-subtype="png" xlink:href="image7.png"/>
      </fig>
      <p id="_paragraph-149"><bold id="_bold-35">Figure 4</bold>. Performance at design velocity</p>
      <p id="_paragraph-150"> normalized the cleanliness factor U/U<sub id="_subscript-217">c</sub> decreases faster compared to and Q/Q<sub id="_subscript-218">0</sub> because of the nature of exchanger operation on the concave part of the ε–NTU curve. A coefficient of this magnitude results in only an 11% reduction in duty, despite being a 20% drop.</p>
      <p id="_paragraph-151">
        <bold id="_bold-36">Table 3</bold>
        <bold id="_bold-37">. The predicted monthly performance at the design velocity (u = 1.5 m s⁻¹)</bold>
        <bold id="_bold-38">.</bold>
      </p>
      <fig id="fig8">
        <label>Figure 8</label>
        <caption>
          <p id="_paragraph-152"/>
        </caption>
        <graphic id="_graphic-8" mimetype="image" mime-subtype="png" xlink:href="image8.png"/>
      </fig>
      <p id="_paragraph-153">The outlet temperatures show in Table 3 and Figure 5 indicate the operational details without interpretation: as the exchanger fouls, the hot stream leaves hotter (71.1 → 82.8 °C), and the cold stream cooler (59.4 → 55.7 °C) due to a decreasing amount of heat exchanged between the two streams. In a pre-heat train this hotter hot-outlet is precisely the signature that downstream furnaces must make up, and it is directly observable, which is what makes the model useful as a soft sensor.</p>
      <fig id="fig9">
        <label>Figure 9</label>
        <caption>
          <p id="_paragraph-154"/>
        </caption>
        <graphic id="_graphic-9" mimetype="image" mime-subtype="png" xlink:href="image9.png"/>
      </fig>
      <p id="_paragraph-155">
        <bold id="_bold-39">Figure 5. </bold>
        <bold id="_bold-40">Evolution of the outlet and film temperatures during fouling at the design velocity.</bold>
      </p>
      <p id="_paragraph-156"> As duty is lost the hot outlet rises and the cold outlet falls; the film (deposition-surface) temperature rises, which feeds back through the Arrhenius term to accelerate early deposition.</p>
      <p id="paragraph-c5604cd98f55d0cc05da5f734567eb30">
        <bold id="bold-8dca79926f7f10afa44940a3eb66faca"> 6.2 Effect of flow rate</bold>
      </p>
      <p id="_paragraph-157">Figure 3 also contains the three velocity cases, and the contrast is the clearest single demonstration of why a condition-dependent model is needed. Raising the velocity from 1.0 to 2.0 m s⁻¹ lowers the asymptotic resistance from 8.83 × 10⁻⁴ to 4.00 × 10⁻⁴ m² K W⁻¹ and shortens the time constant from 67.5 to 16.9 days. The plateau follows the predicted u<sup id="_superscript-28">m−n</sup> = u<sup id="_superscript-29">−1.6</sup> law and the time constant the predicted u⁻² law. A fixed fouling factor would assign all three cases the same resistance and would therefore misrepresent both the severity and the speed of fouling by more than a factor of two. The result is also revealing a real design trade-off: while more velocity mitigates fouling, pumping power increases approximately with the (cube) of velocity, so this requires a punch in at least one axis end model appropriate for exploring an optimum balance.</p>
      <p id="paragraph-a0824dc724df304f0079415c97ac37de">
        <bold id="bold-99f303f7c0a7e45af4d4feec85f8d027">6.3 Effect of temperature</bold>
      </p>
      <p id="_paragraph-158">Figure 6 isolates the two dependences of the asymptotic resistance. The left panel confirms the monotonic decrease of R<sub id="_subscript-219">f</sub><sup id="_superscript-30">*</sup> with velocity; the right panel shows the Arrhenius increase with film temperature, R<sub id="_subscript-220">f</sub><sup id="_superscript-31">*</sup> roughly tripling as the film temperature rises from 120 to 190 °C. Because the film temperature is not an independent input but is set by the thermal state through Eq, and because it rises as the deposit grows, the model captures the self-accelerating character of high-temperature fouling without any additional assumption. This is the mechanism behind the threshold behavior of chemical-reaction fouling and is the reason that, in practice, the hottest exchangers in a train foul the fastest.</p>
      <fig id="fig10">
        <label>Figure 10</label>
        <caption>
          <p id="_paragraph-159"/>
        </caption>
        <graphic id="_graphic-10" mimetype="image" mime-subtype="png" xlink:href="image10.png"/>
      </fig>
      <p id="_paragraph-160"><bold id="_bold-41">Figure 6. </bold>Parametric dependence of the asymptotic fouling resistance. Left: R<sub id="_subscript-221">f</sub><sup id="_superscript-32">*</sup> decreases with tube velocity as u<sup id="_superscript-33">m−n</sup>. Right: R<sub id="_subscript-222">f</sub><sup id="_superscript-34">*</sup> increases with film temperature through the Arrhenius factor of Eq. (26). The two panels quantify the competing shear and reaction effects.</p>
      <p id="paragraph-9e325c12c264605da403b4488d19b8e6">
        <bold id="bold-bbac12f7f62f579517df4f9405204374">6.4 Operating-point shift and sensitivity ranking</bold>
      </p>
      <p id="_paragraph-161">Figure 7 places the clean and fully fouled states on the counterflow ε–NTU chart. Fouling moves the operating point down and to the left along the C<sub id="_subscript-223">r</sub> = 0.316 contour, from (NTU = 1.41, ε = 0.70) to (NTU = 1.12, ε = 0.63). The near-horizontal spacing of the contours in this region is the graphical statement of the attenuation discussed in Section 6.1.</p>
      <fig id="fig11">
        <label>Figure 11</label>
        <caption>
          <p id="_paragraph-162"/>
        </caption>
        <graphic id="_graphic-11" mimetype="image" mime-subtype="png" xlink:href="image11.png"/>
      </fig>
      <p id="_paragraph-163">
        <bold id="_bold-42">Figure 7. </bold>
        <bold id="_bold-43">Counterflow ε–NTU chart with the operating-point shift caused by fouling.</bold>
      </p>
      <p id="_paragraph-164"> The filled circle is the clean state and the open square the fully fouled state; fouling slides the point down the C<sub id="_subscript-224">r</sub> = 0.316 contour. The flatness of the contour at this NTU is why an appreciable loss of NTU produces a smaller loss of effectiveness.</p>
      <p id="_paragraph-165">In Figure 8, and Table 4 we collect the normalized sensitivity coefficients of Section 3.9 evaluated for the case study. Their ranking is directly actionable. Duty is the most sensitive to (S = 1.000, a perfect proportionality) inlet temperature difference, so any drift in hot supply temperature maps 1: 1 onto duty. Flow rate is next (S = 0.706): increasing the minimum-stream flow raises duty, but sub-proportionally, because it simultaneously depresses NTU, the competition made explicit in Eq. The duty responds to the overall coefficient with the same elasticity as the effectiveness responds to NTU (S = 0.463), a consequence of the exact identity of Eq. Finally, the coefficient’s sensitivity to fouling, S<sub id="_subscript-225">Rf</sub><sup id="_superscript-35">U</sup> = −Θ/(1+Θ) = −0.203 at the design asymptote, quantifies how strongly deposition erodes the coefficient and shows that this erosion is itself throttled by the 1/(1+Θ) factor.</p>
      <fig id="fig12">
        <label>Figure 12</label>
        <caption>
          <p id="_paragraph-166"/>
        </caption>
        <graphic id="_graphic-12" mimetype="image" mime-subtype="png" xlink:href="image12.png"/>
      </fig>
      <p id="_paragraph-167">
        <bold id="_bold-44">Figure 8. </bold>
        <bold id="_bold-45">Normalized sensitivity coefficients at the design point (the fouling sensitivity is evaluated at the design-velocity asymptote).</bold>
      </p>
      <p id="_paragraph-168"> Positive bars increase the response variable; the duty is governed most strongly by the inlet temperature difference, then by flow rate, then by the overall coefficient.</p>
      <p id="_paragraph-169">
        <bold id="_bold-46">Table 4.</bold>
        <bold id="_bold-47">Closed-form normalized sensitivity coefficients evaluated for the case study.</bold>
      </p>
      <fig id="fig13">
        <label>Figure 13</label>
        <caption>
          <p id="_paragraph-170"/>
        </caption>
        <graphic id="_graphic-13" mimetype="image" mime-subtype="png" xlink:href="image13.png"/>
      </fig>
      <p id="paragraph-2e56d4dd4da1dd9ee6939f83aab35d72">
        <bold id="bold-a923f49ffdb2287b76e483a1affe67e4">6.5 Uncertainty analysis</bold>
      </p>
      <p id="_paragraph-171">Applying Eqs. (35)–(37) with representative instrument uncertainties 2% on each mass flow, 1% on each specific heat and ±0.5 K on each temperature gives a relative uncertainty of 2.3% in the computed duty and 2.9% in the inferred overall coefficient. Propagated through Eq. (37), the standard uncertainty in the asymptotic fouling resistance is 0.97 × 10⁻⁴ m² K W⁻¹, which is about 18% of the resistance itself. Table 5 summarizes these figures.</p>
      <p id="_paragraph-172">
        <bold id="_bold-48">Table 5.</bold>
        <bold id="_bold-49">Illustrative uncertainty budget (measurement uncertainties: 2% flow, 1% specific heat, ±0.5 K temperature).</bold>
      </p>
      <fig id="fig14">
        <label>Figure 14</label>
        <caption>
          <p id="_paragraph-173"/>
        </caption>
        <graphic id="_graphic-14" mimetype="image" mime-subtype="png" xlink:href="image14.png"/>
      </fig>
      <p id="_paragraph-174">The disproportionate uncertainty in the inferred fouling resistance is not a defect of the model but a warning that the model makes quantitative. Equation (35) shows that the temperature term is amplified by 1/ΔT<sub id="_subscript-226">h</sub>, so an exchanger with a small hot-side temperature changes a close temperature approach will yield a poorly determined fouling resistance from the same instruments. The practical recommendation is that fouling monitoring based on inferred resistance should be treated with appropriate caution on units operating near their temperature pinch, and that the temperature instrumentation on such units repays particular attention.</p>
    </sec>
    <sec id="sec-7">
      <title>Discussion</title>
      <p id="paragraph-b2c1cfa27b528065134646267aeba1f3">
        <bold id="bold-cd2bb479c58a7abbbecd796fe64764fc">7.1 Comparison with established approaches</bold>
      </p>
      <p id="_paragraph-175"><bold id="_bold-50">Against the fixed fouling factor. </bold>The industrial standard remains a constant fouling allowance added once at design. The present model contains that practice as a degenerate special case setting R<sub id="_subscript-227">f</sub> to a constant recovers the fixed-factor result but replaces the constant with a resistance that evolves in time and depends mechanistically on velocity and film temperature. The velocity study of Section 6.2, in which the asymptotic resistance varies by more than a factor of two across a realistic velocity range, shows concretely what the fixed factor discards.</p>
      <p id="_paragraph-176"><bold id="_bold-51">Against threshold models. </bold>The number of surfaces is mechanistically dependent on surface shear and temperature in Ebert and Panchal threshold framework, but it is expressed as a deposition term minus a constant shear-removal term (constant rate below the threshold leading to non-plateauing rates), consistent with the present model. The present model instead follows Kern and Seaton in making removal proportional to the deposit, which yields an asymptotic plateau. The two are complementary: the threshold form is the right description when the design objective is to stay in a no-fouling regime, whereas the asymptotic form is the right description when a stable fouling layer is expected and the question is how much performance is ultimately lost. A practical model could switch between them; here the asymptotic form was chosen because a plateau is the more common industrial observation and because it yields the compact degradation number Θ.</p>
      <p id="_paragraph-177"><bold id="_bold-52">Against distributed dynamic models. </bold>The distributed, first-principles models of Coletti and Macchietto and Diaz-Bejarano resolve the axial variation of fouling, the ageing of the deposit and the two-way coupling with the hydraulics through a moving-boundary formulation, and are the appropriate tools when spatial and compositional detail is required. That fidelity is bought with the numerical solution of coupled partial differential equations and, in practice, dedicated software. The present model is deliberately lumped: it sacrifices axial resolution and deposit ageing in exchange for an analytical, simulator-free formulation whose entire state is a single scalar and whose sensitivities are available in closed form. The two occupy different points on the fidelity cost frontier, and are complementary rather than competing a lumped model of this kind is a natural reduced-order companion to a distributed model, and a natural core for a lightweight digital twin.</p>
      <p id="_paragraph-178"><bold id="_bold-53">Against data-driven models. </bold>Machine-learning predictors of fouling resistance can achieve excellent accuracy within the envelope of their training data, and hybrid monitoring schemes infer foulant behavior from excess loads or embed fouling in advanced control. Their weaknesses are the mirror image of the present model’s strengths: they extrapolate unreliably and offer no analytical sensitivity. Conversely, the present model does not learn from data automatically; its kinetic parameters must be fitted. The most promising route is hybrid using the mechanistic model as a physics-informed backbone whose few parameters are estimated from data which is noted in Section 9.</p>
      <p id="_paragraph-179"><bold id="_bold-54">Against transient ε–NTU treatments. </bold>Time-dependent ε–NTU formulations have been developed for fast transients such as inlet step changes and mass discharge. The present work applies the ε–NTU framework on the opposite, slow time scale of fouling, where the quasi-steady approximation is rigorously justified by the separation of time scales, and couples it to a deposition–removal law rather than to a thermal-inertia term.</p>
      <p id="paragraph-7af186a1ffbd2f6738c603ae40997401">
        <bold id="bold-b6ab53f3b0c095bdfcccc3be5a748ce4">7.2 Strengths</bold>
      </p>
      <p id="paragraph-158bde0a387d9afd362b77c1703b375d">● <bold id="bold-1">Transparency and reproducibility. </bold>Every relation is derived in closed form and every parameter has a physical meaning and an SI unit; another researcher can reproduce the model from Section 3 alone.</p>
      <p id="paragraph-2">● <bold id="bold-2">Analytical sensitivity. </bold>The closed-form coefficients of Eqs give a directly interpretable ranking of design and operating levers that a black-box model cannot provide.</p>
      <p id="paragraph-3">● <bold id="bold-3">A single degradation group. </bold>The number Θ = U<sub id="subscript-1">c</sub> R<sub id="subscript-2">f</sub><sup id="superscript-1">*</sup> collapses the asymptotic loss and converts a performance target into an explicit ceiling on the deposit resistance.</p>
      <p id="paragraph-4">● <bold id="bold-4">Computational economy and independence. </bold>A single scalar ODE with algebraic updates runs in well under a second and needs no commercial simulator, making the model suitable for on-line monitoring and for scanning many operating or design scenarios.</p>
      <p id="paragraph-5">● <bold id="bold-5">Honest uncertainty. </bold>The analytical error propagation exposes, rather than hides, the amplification of measurement error near a close temperature approach.</p>
      <p id="paragraph-02ffe4d4ce9756c74c3431e0412c6a7e">
        <bold id="bold-ed3b25e7d54a99d861311ec2376debba">7.3 Limitations</bold>
      </p>
      <p id="paragraph-6">● <bold id="bold-6">Lumped in space. </bold>A single film temperature and a single fouling resistance represent the whole surface; the axial rise of wall temperature, and therefore the axial variation of fouling, is not resolved. For long units with strong temperature gradients a distributed treatment is preferable.</p>
      <p id="paragraph-7">● <bold id="bold-7">Constant properties and single phase. </bold>Strongly temperature-dependent properties and any boiling or condensation are outside the present scope and would require a step-wise or two-phase extension.</p>
      <p id="paragraph-8">● <bold id="bold-8">No hydraulic coupling or ageing. </bold>The model tracks the thermal resistance of the deposit but not its effect on pressure drop, nor the change of its properties as it ages; both are known to matter in crude-oil service.</p>
      <p id="paragraph-9">● <bold id="bold-9">Asymptotic form only. </bold>The Kern–Seaton closure assumes a plateau; systems showing linear, falling-rate or long induction-period behavior would need a different rate law, although the coupling framework would be unchanged.</p>
      <p id="paragraph-10">● <bold id="bold-10">Parameters require calibration. </bold>The deposition and removal pre-factors and the activation energy must be fitted to plant or laboratory data before quantitative prediction on a specific unit; the case study demonstrates the structure, not calibrated constants for a named fluid.</p>
      <p id="paragraph-11"><bold id="bold-11">Counterflow idealization. </bold>The usual LMTD correction factor or the proper ε–NTU relation would result in multi-pass and cross-flow arrangements; pure counterflow is considered here only.</p>
      <p id="paragraph-3bcbaf5616caf2c49672c8e71d4a28a4">
        <bold id="bold-8509b7bae4da4e244f8096dc2358a2a4">7.4  Industrial applications</bold>
      </p>
      <p id="_paragraph-181">Three applications follow directly from the structure of the model. First, as a soft sensor: from continuously measured flows and terminal temperatures Eqs ensure that an inferred overall coefficient and fouling resistance are continually calculated in real time with the uncertainty of Section 6.5 attached; supplying a physically grounded fouling-monitoring signal. Second, as a cleaning-schedule and screening tool: because the model is cheap and analytical, the degradation trajectory can be extrapolated forward at any combinations of velocity or feed temperature to determine when the accumulated duty loss warrants a clean, while also providing Θ as a one-line comparison metric for ranking possible operating points. Third, as a design aid: the explicit velocity and temperature dependences let the designer choose a velocity that keeps Θ below a target while weighing the cubic pumping-power penalty, rather than relying on a table value that is blind to both. In each case the model’s value is not that it is the most accurate description available, but that it is transparent, differentiable and fast enough to be used routinely.</p>
    </sec>
    <sec id="sec-8">
      <title>Conclusions</title>
      <p id="_paragraph-182">A compact, simulator-independent mathematical model of heat-exchanger performance under fouling has been developed from first principles by coupling the steady-flow energy balance, the LMTD relation and the effectiveness–NTU formulation to an asymptotic Kern–Seaton fouling law whose deposition and removal terms are explicit functions of tube velocity and film temperature. The following conclusions are drawn.</p>
      <p id="paragraph-a61a7604c4f3da0cf310dd4e54821bcb">
        <bold id="bold-da164328d4cb4a096f96cdfb694422c5">Acknowledgements</bold>
      </p>
      <p id="_paragraph-183">The authors gratefully acknowledge the Department of Chemical Engineering, College of Engineering, University of Babylon for supporting this work. No external funding was received.</p>
      <p id="paragraph-8a2ab553eb3b4ada50839803df66883a">
        <bold id="bold-e1a69f295657237e009fde38f320edf9">Conflict of Interest</bold>
      </p>
      <p id="_paragraph-184">The author has declared that no competing interests exist.</p>
      <p id="paragraph-76456a10a709dcb37061adc6940c605a">
        <bold id="bold-7024efcdea1a63245a9103d5bdedd657">Data Availability Statement</bold>
      </p>
      <p id="_paragraph-185">All data that support the findings of this study are directly generated from the governing equations detailed in Section 3 with parameters shown in Table 1, and are therefore fully reproducible from the manuscript itself. The illustrative case-study data are computed, not experimentally measured, and are identified as such throughout.</p>
    </sec>
  </body><back>
    <ref-list>
      <ref id="bib1">
        <element-citation publication-type="journal">
          <day>20</day>
          <issue>8</issue>
          <month>4</month>
          <page-range>4515-4533</page-range>
          <volume>50</volume>
          <year>2011</year>
          <pub-id pub-id-type="doi">10.1021/ie901991g</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Coletti</surname>
              <given-names>Francesco</given-names>
            </name>
            <name>
              <surname>Macchietto</surname>
              <given-names>Sandro</given-names>
            </name>
          </person-group>
          <source>Industrial &amp; Engineering Chemistry Research</source>
          <article-title>A Dynamic, Distributed Model of Shell-and-Tube Heat Exchangers Undergoing Crude Oil Fouling</article-title>
        </element-citation>
      </ref>
      <ref id="bib2">
        <element-citation publication-type="journal">
          <issue>15-16</issue>
          <page-range>1349-1364</page-range>
          <volume>43</volume>
          <year>2022</year>
          <pub-id pub-id-type="doi">10.1080/01457632.2021.1963537</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Lozano-Santamaria</surname>
              <given-names>Federico</given-names>
            </name>
            <name>
              <surname>Macchietto</surname>
              <given-names>Sandro</given-names>
            </name>
          </person-group>
          <source>Heat Transfer Engineering</source>
          <article-title>Assessment of a Dynamic Model for the Optimization of Refinery Preheat Trains under Fouling</article-title>
        </element-citation>
      </ref>
      <ref id="bib3">
        <element-citation publication-type="book">
          <publisher-name>TEMA</publisher-name>
          <year>2007</year>
          <person-group person-group-type="author">
            <collab>
              <named-content content-type="name">Tubular Exchanger Manufacturers Association</named-content>
            </collab>
          </person-group>
          <source>Standards of the Tubular Exchanger Manufacturers Association</source>
        </element-citation>
      </ref>
      <ref id="bib4">
        <element-citation publication-type="journal">
          <issue>1</issue>
          <page-range>43-56</page-range>
          <volume>4</volume>
          <year>1983</year>
          <pub-id pub-id-type="doi">10.1080/01457638108939594</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>EPSTEIN</surname>
              <given-names>NORMAN</given-names>
            </name>
          </person-group>
          <source>Heat Transfer Engineering</source>
          <article-title>Thinking about Heat Transfer Fouling: A 5 × 5 Matrix</article-title>
        </element-citation>
      </ref>
      <ref id="bib5">
        <element-citation publication-type="journal">
          <issue>1</issue>
          <page-range>53-71</page-range>
          <volume>82</volume>
          <year>2004</year>
          <pub-id pub-id-type="doi">https://doi.org/10.1205/026387604772803070</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Yeap</surname>
              <given-names>B L</given-names>
            </name>
            <name>
              <surname>Wilson</surname>
              <given-names>D I</given-names>
            </name>
            <name>
              <surname>Polley</surname>
              <given-names>G T</given-names>
            </name>
            <name>
              <surname>Pugh</surname>
              <given-names>S J</given-names>
            </name>
          </person-group>
          <source>Chemical Engineering Research and Design</source>
          <article-title>Mitigation of Crude Oil Refinery Heat Exchanger Fouling Through Retrofits Based on Thermo-Hydraulic Fouling Models</article-title>
        </element-citation>
      </ref>
      <ref id="bib6">
        <element-citation publication-type="book">
          <publisher-name>John Wiley &amp; Sons</publisher-name>
          <year>2003</year>
          <person-group person-group-type="author">
            <name>
              <surname>Shah, R. K., &amp; Sekulić</surname>
              <given-names>D. P.</given-names>
            </name>
          </person-group>
          <source>Fundamentals of heat exchanger design</source>
        </element-citation>
      </ref>
      <ref id="bib7">
        <element-citation publication-type="book">
          <publisher-name>CRC Press</publisher-name>
          <year>2020</year>
          <pub-id pub-id-type="doi">10.1201/9780429469862</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Kakaç, S., Liu, H., &amp; Pramuanjaroenkij</surname>
              <given-names>A.</given-names>
            </name>
          </person-group>
          <source>Heat Exchangers: Selection, Rating, and Thermal Design</source>
        </element-citation>
      </ref>
      <ref id="bib8">
        <element-citation publication-type="book">
          <publisher-name>John Wiley &amp; Sons, Ltd</publisher-name>
          <year>2018</year>
          <person-group person-group-type="author">
            <name>
              <surname>Theodore L. Bergman, Adrienne S. Lavine, Frank P. Incropera</surname>
              <given-names>David P. DeWitt</given-names>
            </name>
          </person-group>
          <source>Fundamentals of heat and mass transfer (8th ed.)</source>
        </element-citation>
      </ref>
      <ref id="bib9">
        <element-citation publication-type="journal">
          <issue>17</issue>
          <page-range>3255-3264</page-range>
          <volume>46</volume>
          <year>2003</year>
          <pub-id pub-id-type="doi">https://doi.org/10.1016/S0017-9310(03)00118-2</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Yin</surname>
              <given-names>Juan</given-names>
            </name>
            <name>
              <surname>Jensen</surname>
              <given-names>Michael K</given-names>
            </name>
          </person-group>
          <source>International Journal of Heat and Mass Transfer</source>
          <article-title>Analytic model for transient heat exchanger response</article-title>
        </element-citation>
      </ref>
      <ref id="bib10">
        <element-citation publication-type="journal">
          <volume>48</volume>
          <year>2011</year>
          <pub-id pub-id-type="doi">10.1007/s00231-011-0914-5</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Regulagadda</surname>
              <given-names>P</given-names>
            </name>
            <name>
              <surname>Naterer</surname>
              <given-names>G</given-names>
            </name>
            <name>
              <surname>Dincer</surname>
              <given-names>Ibrahim</given-names>
            </name>
          </person-group>
          <source>Heat and Mass Transfer</source>
          <article-title>Time varying NTU method for heat exchanger analysis with mass discharge</article-title>
        </element-citation>
      </ref>
      <ref id="bib11">
        <element-citation publication-type="journal">
          <issue>5</issue>
          <page-range>258–262</page-range>
          <volume>4</volume>
          <year>1959</year>
          <person-group person-group-type="author">
            <name>
              <surname>Kern, D. Q., &amp; Seaton</surname>
              <given-names>R. E.</given-names>
            </name>
          </person-group>
          <source>British Chemical Engineering</source>
          <article-title>A theoretical analysis of thermal surface fouling</article-title>
        </element-citation>
      </ref>
      <ref id="bib12">
        <element-citation publication-type="journal">
          <issue>10</issue>
          <volume>14</volume>
          <year>2024</year>
          <pub-id pub-id-type="doi">10.3390/app14104003</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Čarnogurská</surname>
              <given-names>Mária</given-names>
            </name>
            <name>
              <surname>Příhoda</surname>
              <given-names>Miroslav</given-names>
            </name>
            <name>
              <surname>Andrejiová</surname>
              <given-names>Miriam</given-names>
            </name>
            <name>
              <surname>Tóth</surname>
              <given-names>Lukáš</given-names>
            </name>
          </person-group>
          <source>Applied Sciences</source>
          <article-title>Analysis of the Mathematical Models for Identifying the Thickness of the Fouling Layer in Natural Gas Coolers</article-title>
        </element-citation>
      </ref>
      <ref id="bib13">
        <element-citation publication-type="journal">
          <page-range>451–460</page-range>
          <year>1997</year>
          <person-group person-group-type="author">
            <name>
              <surname>Ebert, W. A., &amp; Panchal</surname>
              <given-names>C. B.</given-names>
            </name>
          </person-group>
          <article-title>Analysis of Exxon crude-oil-slip stream coking data</article-title>
        </element-citation>
      </ref>
      <ref id="bib14">
        <element-citation publication-type="journal">
          <issue>7-8</issue>
          <page-range>669-680</page-range>
          <volume>38</volume>
          <year>2017</year>
          <pub-id pub-id-type="doi">10.1080/01457632.2016.1206407</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Wilson</surname>
              <given-names>D Ian</given-names>
            </name>
            <name>
              <surname>Ishiyama</surname>
              <given-names>Edward M</given-names>
            </name>
            <name>
              <surname>Polley</surname>
              <given-names>Graham T</given-names>
            </name>
          </person-group>
          <source>Heat Transfer Engineering</source>
          <article-title>Twenty Years of Ebert and Panchal—What Next?</article-title>
        </element-citation>
      </ref>
      <ref id="bib15">
        <element-citation publication-type="journal">
          <issue>5</issue>
          <page-range>907-917</page-range>
          <volume>35</volume>
          <year>2011</year>
          <pub-id pub-id-type="doi">https://doi.org/10.1016/j.compchemeng.2011.01.027</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Coletti</surname>
              <given-names>Francesco</given-names>
            </name>
            <name>
              <surname>Macchietto</surname>
              <given-names>Sandro</given-names>
            </name>
            <name>
              <surname>Polley</surname>
              <given-names>Graham T</given-names>
            </name>
          </person-group>
          <source>Computers &amp; Chemical Engineering</source>
          <article-title>Effects of fouling on performance of retrofitted heat exchanger networks: A thermo-hydraulic based analysis</article-title>
        </element-citation>
      </ref>
      <ref id="bib16">
        <element-citation publication-type="journal">
          <issue>1</issue>
          <page-range>90-107</page-range>
          <volume>62</volume>
          <year>2016</year>
          <pub-id pub-id-type="doi">https://doi.org/10.1002/aic.15036</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Diaz-Bejarano</surname>
              <given-names>Emilio</given-names>
            </name>
            <name>
              <surname>Coletti</surname>
              <given-names>Francesco</given-names>
            </name>
            <name>
              <surname>Macchietto</surname>
              <given-names>Sandro</given-names>
            </name>
          </person-group>
          <source>AIChE Journal</source>
          <article-title>A new dynamic model of crude oil fouling deposits and its application to the simulation of fouling-cleaning cycles</article-title>
        </element-citation>
      </ref>
      <ref id="bib17">
        <element-citation publication-type="journal">
          <page-range>326-343</page-range>
          <volume>185</volume>
          <year>2022</year>
          <pub-id pub-id-type="doi">https://doi.org/10.1016/j.cherd.2022.07.011</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Patil</surname>
              <given-names>Parag</given-names>
            </name>
            <name>
              <surname>Srinivasan</surname>
              <given-names>Babji</given-names>
            </name>
            <name>
              <surname>Srinivasan</surname>
              <given-names>Rajagopalan</given-names>
            </name>
          </person-group>
          <source>Chemical Engineering Research and Design</source>
          <article-title>A simple model-based methodology to characterize foulants in heat exchangers using excess thermal and hydraulic loads</article-title>
        </element-citation>
      </ref>
      <ref id="bib18">
        <element-citation publication-type="journal">
          <page-range>142706</page-range>
          <volume>462</volume>
          <year>2024</year>
          <pub-id pub-id-type="doi">https://doi.org/10.1016/j.jclepro.2024.142706</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Zaza</surname>
              <given-names>Afaf</given-names>
            </name>
            <name>
              <surname>Bennouna</surname>
              <given-names>El Ghali</given-names>
            </name>
            <name>
              <surname>Iranzo</surname>
              <given-names>Alfredo</given-names>
            </name>
            <name>
              <surname>Hammami</surname>
              <given-names>Youness</given-names>
            </name>
            <name>
              <surname>Pino</surname>
              <given-names>F Javier</given-names>
            </name>
          </person-group>
          <source>Journal of Cleaner Production</source>
          <article-title>Optimizing sustainability in hybrid cooling towers: Investigating fouling resistance, water quality correlations, modeling, and cleaning strategies for thermal power plants</article-title>
        </element-citation>
      </ref>
      <ref id="bib19">
        <element-citation publication-type="journal">
          <issue>5</issue>
          <page-range>e2811</page-range>
          <volume>17</volume>
          <year>2022</year>
          <pub-id pub-id-type="doi">https://doi.org/10.1002/apj.2811</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>P. K.</surname>
              <given-names>Resma Madhu</given-names>
            </name>
            <name>
              <surname>Subbaiah</surname>
              <given-names>Jayalalitha</given-names>
            </name>
          </person-group>
          <source>Asia-Pacific Journal of Chemical Engineering</source>
          <article-title>Iterative quality weighted interpolation for LPV-MPC control of industrial heat exchanger under varying fouling conditions</article-title>
        </element-citation>
      </ref>
      <ref id="bib20">
        <element-citation publication-type="journal">
          <page-range>115973</page-range>
          <volume>181</volume>
          <year>2020</year>
          <pub-id pub-id-type="doi">https://doi.org/10.1016/j.applthermaleng.2020.115973</pub-id>
          <person-group person-group-type="author">
            <name>
              <surname>Aiello</surname>
              <given-names>Victor C</given-names>
            </name>
            <name>
              <surname>Kini</surname>
              <given-names>Girish</given-names>
            </name>
            <name>
              <surname>Staedter</surname>
              <given-names>Marcel A</given-names>
            </name>
            <name>
              <surname>Garimella</surname>
              <given-names>Srinivas</given-names>
            </name>
          </person-group>
          <source>Applied Thermal Engineering</source>
          <article-title>Investigation of fouling mechanisms for diesel engine exhaust heat recovery</article-title>
        </element-citation>
      </ref>
    </ref-list>
  </back></article>